Harmonic Synthesiser & Network Impact

Pick a load, watch harmonics build, and see the transformer heat, the neutral overload, the LV voltage distort, and capacitors resonate · 50 Hz · IS / IEC / IEEE

Transformer & system

enter your site — short‑circuit, distortion, neutral, heating and resonance are calculated live
60%
1

Fundamental — current & voltage (50 Hz)

I₁ + V₁
2

Harmonic content — current & voltage (Σ 2…50)

3

Total distorted — current & voltage

f

Harmonic spectrum (% of fundamental)

Speed1.0×

Harmonic sliders

AUTO · 6‑pulse VFDharmonics follow the load type and scale with non‑linear %.
Positive (h = 1, 4, 7…) Negative (2, 5, 8, 11…) Zero · triplen (3, 9, 15…)
OrdMagnitude%A rmsPhase°
1Fund.1000° · reference

Point of Common Coupling (PCC) — IEEE 519‑2022 assessment

HV side · 95th‑percentile basis
Isc @ PCC
short‑circuit
IL (12‑mo demand)
max demand
Isc / IL
→ TDD limit
IEEE 519‑2022 current limits for this Isc/IL band (% of IL)
Assessed on the 95th‑percentile short‑time basis (THD‑I & absolute harmonic current relative to IL). Individual‑order and TDD limits scale with the short‑circuit stiffness Isc/IL — Table 2 (≤69 kV), halved per Table 3 above 69 kV. Voltage limit per Table 1.

LV bus — distortion & currents

at the transformer secondary
LV full‑load current IFLC
LV Isc · total Z (source + Tx)
Harmonic current drawn (LV)
Distortion power D (non‑active VA)

Hot‑spot temperature & estimated harmonic thermal stress

N
°C hot‑spot
40°C110°C ageing
Indicative hot‑spot from loading + harmonic eddy (∝ h²) + triplen neutral heating (IEEE C57.110 / C57.91 trend). K‑factor = Σ(Iₕ²h²)/ΣIₕ²; specify a transformer rated ≥ the computed K.

Power factor @ LV bus

displacement & true PF — dual‑reading meter
True power factor (PF = DPF × distortion)
Displacement PF (DPF = cos φ₁)
Solid needle = true PF · dashed = displacement PF. True PF carries the harmonic penalty; a tuned (LC) bank lowers upstream THD‑I and lifts true PF, a plain bank at resonance does the opposite.

Estimated parallel resonance & system harmonic impedance

capacitor OFF
Estimated parallel resonance frequency
Resonant harmonic order
Switch the capacitor on to assess resonance.
kVA demand released (capacity freed)
Transformer copper‑loss saving
THD‑V amplification
Capacitor current loading
System harmonic impedance Z(h) — peak = parallel resonance
Blue = no capacitor (≈ h·X). Amber = with capacitor — the peak is where C resonates with the source/transformer L. Dots mark the harmonics your load injects. Danger when a dot sits under the peak.

Harmonic energy loss — three‑phase total

additional ACTIVE power (real, billable kWh) dissipated as heat — IEEE C57.110
estimated additional active loss — heat (kW, 3‑phase)
…added on top of load losses at this load
K‑factor (FHL) · FHL‑STR
Max continuous loading (C57.110 capability)
Where the loss goes
Per IEEE C57.110‑2018 harmonic loss factors: DC I²R (∝ harmonic rms²) + winding eddy PEC·FHL (∝ h²) + other stray POSL·FHL‑STR (∝ h^0.8, tank/clamps) + the external neutral conductor IN²·RN (a cable loss, not a winding loss — the triplen currents in the phase windings are already counted separately, so this is not double‑counted). Uses the harmonic current that actually flows in the transformer (load injection × source/capacitor current divider), so a plain‑cap resonance raises the loss and a tuned reactor lowers it. These are active losses (real, dissipated as heat) — distinct from the non‑active distortion power D under power factor. Estimated values: rated load loss = measured Pk when entered, else %R·kVA with %R = %Z/√(1+(X/R)²); PEC/POSL are typical split fractions and %R is referenced to 75 °C (IEC 60076‑1) — substitute manufacturer test data for an exact figure.
Method & standards. LV S/C Ztot=%Z/100 + Stx/Sfault · HV ratio Isc/IL=Sfault/Sdemand (IL = 12‑month max demand) · TDD assessed at the HV PCC (≤69 kV → IEEE 519 Table 2; 69–161 kV → Table 3) — not at 415 V · neutral IN=3·√Σ I3,9,15…² (zero‑sequence triplens) · heating via K‑factor K=Σ(h²Ih²)/Σ Ih², eddy loss ∝ h²Ih² · parallel resonance hr=√(Ssc/Qcap), fr=50·hr.
IEEE 519‑2022 (limits) · IEEE C57.110‑2018 (transformer derating) · IEC 61000‑4‑7 / 61000‑3‑6 / 61000‑2‑4, IEC 60076‑7 (loading), IEC 60364‑5‑52 (neutral sizing), IEC 60871 / IEEE 18 (capacitors) (IEC) · IS 2026 / IS 3043 (BIS).
Hot‑spot and resonance amplification are indicative teaching trends (damped), not certified ratings; eddy model is conservative above the 25th order per IEEE C57.110.
Foretec Electric India Pvt Ltd, Coimbatore — A teaching synthesiser for field‑ready power‑quality engineers — www.foretecelectric.com
⊞ Generate PDF report ↗